Can a robot cell door be left open when not is use - for instance when an employee goes on break, they leave the door open and the robot is not locked out? I am looking for safety guidelines on this.

3 Answers

  • = Company Profile
  • = Answered Questions

Albert Keefer - Technical Sales Engineer
Chicago Electric
akeefer [at] chicagoelectric [dot] com
(630) 784-0800

Dear Sir: Thank you for your inquiry, Proper and thorough response to safety related questions would not be possible with limited information. As a turnkey integrator, we would not be in a position to certify safety aspects of any installation where we are not integrally involved in in all implementation details. I can reference ANSI/RIA R15.06-2012 Industrial Robot Safety Standard as a good first step toward answering your questions. Please consider us should you determine that a turnkey solution is needed or if you would be interested in having us evaluate the application please feel free to contact me directly. FYI I am out in your area the first week of February let me know if you would like me to stop in Thank you and best wishes on your project. Al Keefer 847 954 9365

James Norton - President
JHN Group
jamesnorton [at] jhngroup [dot] com
(617) 448-9649

The issue would be does it constitute an alternative method to LOTO as defined in ANSI/ASSE Z244.1 - 2003 (R2008) Control of Hazardous Energy Lockout/Tagout and Alternative Methods. Could an unauthorized, untrained person be placed in harms way if they were to enter the cell and close the door behind them. A better way would be to use an alternative method be used, that was short of a full lockout tagout but would not allow an unauthorized person to enter the cell or be put in harms way. A trap key system with the master key under the control of the authorized operator be a solution In any case a risk assessment of the condition should be done to answer the question of what harm if any could happen.

Gregg Wheeler - Director
ZETA Group Engineering LLC
gregg [dot] wheeler [at] zetagroupeng.com
920-336-9382

When a safety fence is required to run a robotic cell, the short answer is no. The cell doors need to be closed in order for the safety control system to reset and allow the robotic system to start back up. There may be areas that are on their own safety circuit and that would then allow this to happen, but this would then have other measures to protect the operator, assuming it was done correctly. Having said all that, if the door is open then the system is not in operation. Your company may have policies around how to stop a system or what needs to be in place when a system is down/not in use.